The Eliwell SB655/C (often part of the Energy Flex series) is a universal parametric controller designed for centralized air-conditioning units, chillers, and heat pumps. Its manual provides critical guidance on managing up to two refrigeration circuits and balancing up to four compressor power steps. Core Capabilities & Technical Profile
According to the SB655 technical data sheet, the controller is engineered for complex HVAC/R environments:
Compressor Management: Supports Scroll, Semi-Hermetic, and Screw compressors with balanced operating hours.
Multi-Input Flexibility: Features 5 sensor inputs compatible with NTC, 4–20 mA, and 0–10 V signals.
Output Configuration: Includes 6 relay outputs and supports variable frequency drives (VFD) for both compressors and water pumps.
Climate Intelligence: Includes automatic summer-winter changeover and "Free Cooling/Heating" logic to optimize energy based on outdoor conditions. User Interface & Navigation
The Energy Flex manual highlights a 4-digit display with 18 icons. Access is divided into three security-coded levels: End User: Basic monitoring and setpoint adjustments. Service: Maintenance settings and alarm history viewing.
Constructor: Deep configuration of digital and analogue outputs. Programming & Monitoring
Copy Card: A physical "Copy Card" can be used to upload or download parameter maps between devices without manual entry.
Communication Protocols: The SB655/C natively supports Modbus RTU and Televis, allowing for remote monitoring and integration into building management systems. eliwell sb655 c manual
Alarms: Common codes such as E1 (cell probe error) or E2 (defrost probe error) indicate shorted or interrupted sensors.
For full configuration tables and wiring diagrams, you can refer to the official Eliwell documentation or technical manuals provided by specialized retailers like Electric Automation Network.
Electronic controllers for centralised air-conditioning units
The Eliwell SB655/C is a base electronic controller typically used in centralized air-conditioning units. This guide provides a summary of essential operations, programming steps, and common alarm codes based on official documentation from Eliwell. 1. Programming & Navigation
To modify the behavior of the unit, you must access the internal parameter menu.
Accessing the Full Menu: Press and hold the SET button for more than 5 seconds until the display shows "PA2".
Entering the Security Code: Press SET twice to reach the code entry screen. Use the Up Arrow to enter code 22, then press SET to confirm.
Modifying Parameters: Use the arrow buttons to scroll through the settings. To change a specific value, press SET, adjust with the arrows, and press SET again to save.
Exiting: Press the Power Button to return to normal operation. 2. Common Alarm & Error Codes
When the controller detects an issue, it will display a code on the screen. Below are the most common alerts for this series: Probable Cause E1 Cell Probe Error
Probe is shorted, interrupted, or incorrectly selected (Parameter H00). E2 Defrost Probe Error Faulty defrost probe circuit or out-of-range settings. E3 Display Probe Error Faulty display probe or incorrect probe type configuration. E7 Link Error End of Manual
No communication between Master and Slave units; check wiring and addresses. E10 Clock/Battery Error
Buffer battery power-off hours exceeded; reset day/time parameters. 3. Key Technical Specifications
Mounting: Designed for panel mounting with a 29x71 mm cutout.
Digital Outputs: Features configurable digital outputs (DOL/AOL) for controlling external components like compressors or fans.
Connectivity: Includes a TTL serial port on the left side for connection to programming keys or monitoring systems. 4. Maintenance Tips
Manual Reset: Some pressure switch alarms require a manual reset using parameter rPA or a direct reset on the device itself.
Environmental Care: Ensure the cooling slots remain unobstructed and avoid mounting in high-moisture or excessively dirty areas.
Parameter Backup: Use an Eliwell multi-function key (mFK) to download and save parameter maps before making major changes.
For the full technical datasheet or firmware updates, you can visit the official Eliwell Product Page.
SB65023511400 ELIWELL BASE SB655/C Electronic controls for..
If the controller behaves erratically due to misconfigured parameters, perform a hard reset: Note: This manual is based on standard Eliwell
If the unit remains locked, power cycle the controller (disconnect power for 30 seconds).
A frequent frustration for users is finding that parameters cannot be changed. This is usually due to the Pr1 (Password/Protection) setting found in the "c" (Configuration) or "Pr" menu in the manual.
If you cannot change settings, navigate to the parameter map, find Pr1, and ensure it is set to 0.
Note: Always disconnect power before wiring.
| Terminal | Function | Typical Connection | | :--- | :--- | :--- | | 1 | Probe 1 (PTC/NTC) – Common | Brown wire of NTC probe | | 2 | Probe 1 (PTC/NTC) – Input | Blue wire of NTC probe | | 3 | Probe 2 (Evaporator) – Input | Second probe wire | | 4 | Probe 2 Common (linked to terminal 1) | Link wire to terminal 1 | | 5 | Digital Input (Door switch) | Door switch (NO/NC) | | 6 | Alarm Relay (NO) | External buzzer/light | | 7 | Alarm Relay (Common) | Neutral for alarm | | 8 | Compressor Relay (NO) | Compressor contactor coil | | 9 | Compressor Relay (Common) | Main power neutral (to compressor) | | 10 | Defrost Relay (NO) | Heater or solenoid valve | | 11 | Defrost Relay (Common) | Neutral for defrost | | 12 | Power Supply (Neutral) | Mains Neutral (N) | | 13 | Power Supply (Live) | Mains Live (L) |
Critical Warning: The SB655 C uses a "common" system for probes. Terminal 1 and terminal 4 must be connected via a jumper wire if using two probes. This is a common installation mistake.
In the world of refrigeration and HVAC control, few names carry as much weight as Eliwell, a brand now part of the Schneider Electric family. Among their most iconic and widely used products is the Eliwell SB655 C. This parameterizable electronic controller is the brain behind countless commercial refrigerators, freezer rooms, beverage coolers, and industrial refrigeration units.
If you have landed on this page searching for the "Eliwell SB655 C manual", you are likely facing one of three scenarios: you are installing a new unit, you need to reprogram an existing controller after a power surge, or your refrigeration unit is displaying an error code and beeping incessantly.
This comprehensive article serves as an extended manual. We will cover everything from hardware overviews and wiring, to programming parameters, common error codes, and where to find the official PDF manual.
The manual includes:
Missing: